Voltage‑Withstand and Partial‑Discharge Testing
for Medium‑ to High‑Voltage (MV–HV) distribution systems—especially underground cables
Test Objectives
- Verify insulation strength—ensure the cable can withstand high voltage without breakdown.
- Detect internal defects—such as voids, air pockets, contamination, or manufacturing damage.
- Confirm overall insulation integrity before installation or energization.
Test Principles
1. AC Withstand Test
The cable is subjected to an over‑voltage AC stress (50/60 Hz) significantly above its service rating:
- Apply 3.5 × U₀ for 5 minutes
(U₀ = phase‑to‑earth rated voltage) - Example: a 12/20 kV cable is tested at 3.5 × 12 kV = 42 kV.
2. Partial Discharge (PD) Test
- Raise the voltage to 2.0 × U₀, then reduce to 1.73 × U₀.
- A PD detector records discharge activity inside the insulation, expressed in pC (pico‑coulombs).
Acceptance Criteria
- AC Withstand: Pass if no breakdown occurs during the 5‑minute test.
- Partial Discharge: Measured PD must not exceed 10 pC.